Limits
pub struct Limits
The limits one band is evaluated against.
All values are in the signal's own unit: a temperature in the SDK's
temperature unit (Celsius unless crate::set_temperature_unit
chose Fahrenheit), volts or milliamps for an analog channel,
whatever you published for an application value.
low and high are values of the signal. hysteresis, delta
and epsilon are distances, so on a temperature they are
differences in degrees of that unit (kelvin-sized in Celsius,
Fahrenheit-sized in Fahrenheit), never offset by 32. On a standard
deviation, and on every limit of a rule with a reference (which
tests the input minus the reference), all five are differences.
Limits — fields
low: f32
Lower limit.
high: f32
Upper limit.
hysteresis: f32
Release deadband.
The value must come back this far past the limit before the band drops. This is what stops an alarm chattering on a value sitting exactly on its threshold, and leaving it at zero is the most common cause of an alarm log full of noise.
delta: f32
For Compare::Changed: the smallest change that counts.
epsilon: f32
For Compare::Equal: the tolerance around high.
Limits — methods
pub fn above(high: f32, hysteresis: f32) -> Self
Alarm above a threshold, with a release deadband.
pub fn below(low: f32, hysteresis: f32) -> Self
Alarm below a threshold, with a release deadband.
pub fn band(low: f32, high: f32, hysteresis: f32) -> Self
A band between two values.